Overview

The CD295 is a two-line, 32-character LCD for use with PakBus data loggers. It displays one real-time value, a description, and units. The CD295 is mounted in an enclosure lid, allowing you to view data on site without opening the enclosure. PC295 software is included for entering descriptions, choosing units, and specifying up to 30 public variables to display. Two buttons on the CD295 are for scrolling through the specified values.

The CD294 is a similar display that is supports mixed-array data loggers.

Key Advantages

Easy, Saves Time
Access data logger data without opening enclosure

Technical Description

The CD295 DataView II is a two-line, 32-character LCD that can display real-time data from a PakBus data logger (see Compatibility information on the web page). Mounted in an enclosure lid, the CD295 allows you to view data without opening the enclosure. The display side of the CD295 is weatherproof. A stainless-steel cover is provided to help protect the display from the effects of ultraviolet radiation.

With the CD295, you can scroll through up to 30 public variables to view the latest measured value, its description, and units of measure. The poll rate is synchronized with the data logger's execution interval, allowing the values to be updated as they are measured. PC295 software is provided with the CD295.

Benefits

  • Compatible with our CR200-series, CR800, CR850, CR1000, and CR3000 dataloggers
  • View real-time data without opening enclosure

Specifications

Display/Keyboard Description
2 lines x 32 characters display and 2-button keyboard
Power Requirements
Powered from the data logger
Relative Humidity
IP65 (when using supplied sealant)
Temperature Range
-20° to +55°C

(operating)

-25° to +70°C

(asleep)

Dimensions
10 x 13.0 x 3 cm

(3.9 x 5.1 x 1.2 in.)

Weight
235 g

(8 oz)

Current Drain

Asleep
1 mA
Active
3 mA

(without backlight)

30 mA

(with backlight)

Ships With

(6)
  • CD Containing PC295 Software
  • Drilling/Mounting Template
  • Power Cable from original mfg
  • Programming cable from original mfg
  • Screw, nut, washer, & rubber gaskets from original mfgQty 4
  • Stainless Steel Door Kit from original mfg

Compatibility

Data Logger Considerations

The CD295 is a PakBus device with a default PakBus address of 4090. In turn, it uses PakBus communications to retrieve data from the attached data logger. The CD295 does not support PakBus Encryption.

Version 2 or higher

The original release of the CD295 operating system (version 1) and PC295 software (version 1) supported only the CR200-series dataloggers. Version 2 of the CD295 operating system (OS) and PC295 added support for the CR1000, CR800, CR850 and CR3000 dataloggers, as well as support for their new data types (long integers, Booleans, strings, and time stamps). To use the new capabilities, customers with version 1 need to upgrade both their CD295 OS and PC295 software.

Use in Enclosures

The display is mounted in the lid of our enclosures. Installing the CD295 in an enclosure lid allows the user to view real-time data on-site without opening the enclosure. The display side of the CD295 is weatherproof. A stainless-steel cover is provided to help protect the display from the effects of ultraviolet radiation.

The 18132 is a common accessory for our standard enclosures. When the 18132 is ordered, Campbell Scientific will install the CD295 in the enclosure lid before the enclosure leaves the factory. Alternatively, the user can do the installation; O-rings, screws, and a drilling template are included with CD295 for this purpose.