Can multiple SDM-CD8S or SDM-CD16S devices be connected to a single data logger?

Yes. SDM devices are addressable. Multiple SDM devices can be connected to a data logger, as long as they all have a unique SDM address. Valid addresses are 0 through 15. Address 16 is reserved for SDM devices that support the Group Trigger Command. The address is set using the rotary switch on the face of the SDM-CD8S or SDM-CD16S.