CURS100

100-Ohm Current Terminal Input Module
CURS100

CURS100

Orderable

100-Ohm Current Terminal Input Module

Model:
CURS100
Item Number:
20598
Warranty:
1 year

Overview

The CURS100 enables your Campbell Scientific data logger to measure a sensor or output device that outputs a current signal (for example, 4 to 20 mA). It converts the current signal to a voltage signal.

Key Advantages

Expands Capabilities
Allows data logger to measure additional types of sensors

Technical Description

The CURS100 uses a 100 Ω resistor for the current shunt that allows currents up to 25 mA to be read on a ±2500 mV range (CR10X, CR510) and currents up to 50 mA to be read on a ±5000 mV range.

Schematic for CURS100

CURS100-to-Sensor Hookup

Benefits

  • Easy to install or remove
  • Connects directly into data logger input terminals
  • Low power consumption

Specifications

Used With
Sensors that output a current signal (4 to 20 mA)
Resistance
100 Ω

(shunt—bulk metal foil)

Tolerance
±0.01%

(@ 25°C)

Power Rating
0.25 W
Maximum Temperature Coefficient
±0.8 ppm/°C
Dimensions
1.5 x 1.5 x 2.7 cm

(0.6 x 0.6 x 1.0 in.) for body with prongs

Weight
6 g

(0.2 oz)

Compatibility

Multiplexers

Our multiplexers are compatible with the CURS100.

Data Logger Considerations

Current CR10X Wiring Panels can accommodate both the CURS100 and the cover associated with the CR10XTCR (reference thermistor for thermocouple measurements). Specifically, the physical configuration of the thermocouple cover, the data logger input terminals, and the terminal input modules allow sufficient room for the cover to be used with the CURS100 attached. In contrast, older CR10TCR covers are not deep enough.

Note: The CR6 (serial number >7501), CR1000X, CR350, CR300, and CR310 data loggers can do current measurements without the CURS100. 

Programming

The CURS100 output is measured with VoltDiff Instruction in CRBasic and with Instruction 2 (Differential Voltage) in Edlog. The CURS100 consumes one differential analog input; an adjacent analog ground channel accepts the analog "ground prong" of the CURS100. Not all data logger terminal strips have this sequence on all channels, so please check your data logger's wiring panel to confirm channel assignments, especially if you plan to use multiple terminal input modules.