If an existing wind set is replaced with a wind monitor (05103-L, 05103-45-L, 05106-L, 05305-L), will more than the multiplier and offset have to be changed in the data logger program?

The measurement instructions will likely remain the same. However, in addition to the multiplier and offset, the type of pulse may change for the wind speed, and the excitation voltage may change for the wind direction. For an explanation of how the data logger needs to be programmed, see the instruction manual.